online UPS 3KVA

FOB Reference Price:Get Latest Price
10 Piece/Pieces (Min. Order)
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Guangdong, China (Mainland)
Brand Name:
EVERON
Model Number:
XPC 1103L
Phase:
Single Phase
Protection:
Short Circuit
Output Voltage:
220/230/240Vac
Type:
On-line
Application:
Security / Monitoring / Alarm
Power Factor:
0.8
Transfer Time:
Normal to battery mode: 0ms, Bypass mode to normal : 0ms
Input Voltage range:
(110+/-5 to 296+/-5)VAC
Overload Capability:
100%+/-5% to 150+/-5%: 30s to bypass; 150+/-5%: 300ms to bypass
Packaging & Delivery
Packaging Details
carton box
Lead Time :
Shipped in 0 days after payment

Specifications

True online, double conversion
Pure sinewave output
LCD display
Settable charging current on LCD
Long backup

 Quick Details

Place of Origin:Guangdong China (Mainland)Brand Name:EVERONModel Number:XPC Series
Type:On-lineApplication:

Workstations,Networking

Capacity:1KVA-3KVA
Phase:1:1 phaseOutput Power Factor:0.8Feature:has matching battery Cabinets(optional)

Commun

ication:

RS232+Intelligent Slotoperation mode:ECO modeCertification:CE, ISO9001

Features

  • True online double conversion completely isolates the load from various grid faults and pollution
  • Digital control technology provides high performance and system reliability
  • Advanced IGBT-based the latest rectifier and inverter technology, high input power factor and low output harmonic
  • Extra-wide input voltage and frequency range adapts adverse grid environment, compatible with diesel generator
  • Intelligent battery management with directly checking and setting charge and discharge of battery on LCD extends battery life
  • Unique dual protection function with hardware and software provides comprehensive protections
  • Direct DC cold start function offers emergency on ups by battery without utility power
  • Large LCD display monitor various real-time information at a glance
  • Multiple monitoring and alarm functions available with dry contact for common alarms and RS232 for remote monitoring and SNMP card(optional) for web-based monitoring

Technical Datas

ModelXPC 1101XPC 1101LXPC 1102XPC 1102LXPC 1103XPC 1103L
Rated Power1KVA/800W2KVA/1600W3KVA/2400W
Input
PhaseL+N +G
Input Voltage(110±5 to 296±5)Vac
Input Frequency(45±0.5 to 55±0.5)Hz
Input PF>0.98
Bypass Voltage(80±5 to 264±5)Vac
Output
Output Voltage220/230/240Vac±2%
Output Power Factor0.8
Output Frequency45Hz~55Hz, same with utility power; <45Hz and >55Hz, lock 50Hz Battery mode: 50/60(1±0.2%)Hz"
THDTHD<3% (linear load)~THD<5% (Non-linear)
Transfer TimeNormal to battery mode: 0ms, Bypass mode to normal : 0ms
Overload Capability105±5%<Load<150±5%: 30s to bypass; >150±5%: 300ms to bypass;
Battery
Battery Voltage36Vdc72Vdc96Vdc
Backup Time (Full/Half Load)>5min(depends on battery capacity for L type)
Charging voltage41.2±0.5V82.5±1V110±1V
Overvoltage43.2V86.4V115.2V
Charging Current1A/7A(L type can set the charging current)
System
RestartAfter turning off due to cut off voltage of battery, UPS will restart,
when voltage is in (175±5~286±5Vac) and frequency is in (45~55Hz)
Efficiency>88%>90%
CommunicationRS-232 + Intelligent Slot
Noise (1m front)<45dB<50dB
Operation Temperature0°C to 40°C
Humidity0~95% non-condensing
Storage Temperature-40°C to 50°C
Altitude1000m
Dimension(W*D*H mm)140*360*210195*455*330
Net Weight(kg)12.56.527163316

  

  

 

  **********************************************************************************************************************************